15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
12. Installer settings
12.2 Settings relating to a heating circuit
* The line or title is only displayed for the options, circuits or
sensors actually connected.
At the end of the intervention, the data is stored after 2 minutes
or by closing the flap.
Press Display Parameter set
Factory
setting
Adjustment
range
Customer
setting
J
then
I
#FITTER PARAM. Setting parameters specific to the installation using
keys
or
.
BUILD. INERTIA Characterisation of building's inertia
3 (22 hours)
0 (10 hours) to
10 (50 hours)
CIRC.CURVE A * Gradient in circuit A 1.5 0 to 4
ROOM INFL. A * Influence of room sensor A 3 0 to 10
CIRC. A: HEAT Use as a direct heating circuit HEAT
HEAT
H.TEMP
DISAB.
H.TEMP Used to control circuit A at a constant temperature
throughout the year (without taking the summer shutdown
into account). Set the parameters TPC D and TPC N.
DISAB. No data for circuit A is displayed
PUMP A PUMP.A Using the P.A. output pump for direct circuit commands
PUMP.A
PUMP.A
BOILER
BOILER Using the output pump P.A. for primary pump commands.
CIRC.CURVE B * Gradient in circuit B 0.7 0 to 4
ROOM INFL. B * Influence of room sensor B 3 0 to 10
CIRC. B: HEAT Use of heating circuit with valve
HEAT
HEAT
SWIM.P.
SWIM.P. Using the circuit for pool management
CIRC.CURVE C * Gradient in circuit C 0.7 0 to 4
CIRC. C: HEAT Use of heating circuit with valve
HEAT
HEAT
BUF.TK.
BUF.TK. Using the circuit to control a storage tank
ROOM INFL. C Influence of room sensor C 3 0 to 10
S.AUX: PUMP A
Use of the auxiliary outlet to control the pump on circuit A
.
PUMP A
PUMP A
ORDER BURN
THERM
DHW LOOP
PROGRAM.
FA.MCBA
ORDER
BURN
The auxiliary outlet is controlled in parallel with the burner
start-up request (
D
). Safety lockdown does not deactivate
this outlet.
DHW LOOP
Use as a domestic loop pump.
PROGRAM. Use as an independent programmable outlet.
THERM Connecting a DHW thermostat to the telephone remote
control input.
FA.MCBA The auxiliary outlet is used to defer the alarm from the box
(outlet 230V).
O.DHW:
PUMP Using a tank load pump on the DHW PUMP outlet.
PUMP
PUMP
I.V
I.V Using a reversal valve for DHW production A used with
pump A
9
.