15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
9. Commissioning
9.4 Adapting the output
Setting the burner output
By setting the boiler output percentage, you obtain an adaptation of
the maximum load in heating mode.
Z
See chapter Table Installer settings, #LIMITED TEMP.,
MAX.R.HEAT(%)
For the hot water mode, the burner is preset to maximum load in the
factory.
9.5 Programming boiler control
Set the integrated control in compliance with the corresponding
operating instructions.
9.6 Domestic hot water preparation
Setting the domestic water temperature:
` Press the
2
key.
` Set the temperature using keys + and - (10-80 °C).
` Save the temperature by pressing the AUTO key.
9.7 Train the user of the installation
9.8 Filling in the commissioning certificate
Z
See "Filling in the commissioning certificate".
9.9 Turning the installation off
` Switch the On/Off switch on Off.
` Close the gas valve.
Output (kW) (Hi / Hs)
Control value
(%)
DTGE130-35 DTG130-35 DTG130-45 DTG130-65 DTG130-90 DTG130-115
33.5 / 37.2 33.5 / 37.2 41.2 / 45.7 62.0 / 68.8 86.0 / 95.5 110.2 / 122.3 100
30.8 / 34.2 30.8 / 34.2 37.9 / 42.1 57 / 63.3 79.1 / 87.8 102.1 / 113.3 90
28.1 / 31.2 28.1 / 31.2 34.6 / 38.4 52 / 57.7 72.2 / 80.1 93.2 / 103.5 80
26.8 / 29.7 26.8 / 29.7 33 / 36.6 49.6 / 55.1 68.8 / 76.4 88.8 / 98.6 75
25.5 / 28.3 25.5 / 28.3 31.3 / 34.7 47.1 / 52.3 65.4 / 72.6 84.4 / 93.7 70
22.8 / 25.3 22.8 / 25.3 28 / 31.1 42.2 / 46.8 58.5 / 64.9 75.5 / 83.8 60
20.1 / 22.3 20.1 / 22.3 24.7 / 27.4 37.2 / 41.3 51.6 / 57.3 66.6 / 73.9 50
17.4 / 19.3 17.4 / 19.3 21.4 / 23.8 32.2 / 35.7 44.7 / 49.6 57.7 / 64.0 40
14.7 / 16.3 14.7 / 16.3 18.1 / 20.1 27.3 / 30.3 37.8 / 42.0 48.8 / 54.2 30