DeDietrich G25 Manual de servicio Pagina 71

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 92
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 70
71
15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
15. Maintenance
15.2.2 Setting the ignition electrode
- Check the setting of the ignition electrode
.
Set the gap between the
ignition electrodes: 3 to 4 mm
.
15.2.3 Checking the hydraulic pressure
The hydraulic pressure must be a minimum of 0.8 bars
.
We
recommend filling the installation to around 1.5 bars higher than the
static height
.
15.2.4 Checking the ionization current
` Tilt the flap on the control panel
.
` Press key
%O
and
$P
simultaneously for 2 seconds
.
` Use keys + and - to switch from
to
-
:
Maximum boiler output
-
:
Minimum output
` In the display area:
EMISSION MES. 88.8°: Boiler temperature
EMISSION MES. 8888: Fan speed
EMISSION MES. 88.8uA: Ionization current
Vista de pagina 70
1 2 ... 66 67 68 69 70 71 72 73 74 75 76 ... 91 92

Comentarios a estos manuales

Sin comentarios