DeDietrich G25 Manual de servicio Pagina 41

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 92
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 40
41
15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
9. Commissioning
` Switch on the electrical supply.
` Starting the burner up.
The appliance must be powered by a circuit containing an omnipolar
switch with an opening distance 3 mm.
The earth connection shall comply with standard NF C 15 100.
Take the boiler up to maximum power.
` Open the panel flap.
` Press key
%O
and
$P
simultaneously for 2 seconds.
` Set the burner output using the + and - keys.
= Maximum power of the burner.
` Remove the plastic plug from the measurement tube.
` Check the CO
2
and O
2
level in the flue gases using the
measuring device.
Check the burner setting to ±0.3% CO
2
; ±0.5% O
2
.
If the values exceed the tolerances:
Check the gas input pressure.
Check that the diaphragm fitted is suitable for the gas
being used (G25 = Diameter 9.8, G20 = Diameter 8.6,
Propane = Diameter 6.7).
1
C001245
CO
2
content (%) O
2
content (%)
Natural gas G20 9 4.8
Natural gas G25 9.5 3.9
Propane 10.0 5.7
Vista de pagina 40
1 2 ... 36 37 38 39 40 41 42 43 44 45 46 ... 91 92

Comentarios a estos manuales

Sin comentarios