De Dietrich Gas 310/610 ECO Serieswww.dedietrichboilers.comG310E 01 v1.0 04/2010Installation and Operating ManualGas-Fired Condensing Hot Water Boiler
9 De Dietrich Gas 310/610 ECO e. Flue gas damper (optional for Gas 310 boiler, standard for Gas 610 boiler) 3.2 OPERATING PRINCIPLE Combu
10 De Dietrich Gas 310/610 ECO 4 TECHINCAL DATA 4.1 Dimensions fig. 03 Elevation drawings Flow connection 3 inch ANSI 15
11 De Dietrich Gas 310/610 ECO 4.2 GAS 610 ECO TECHNICAL DATA Top (plan) view= P == Q == R =AC= D =
12 De Dietrich Gas 310/610 ECO Gas 610 ECO Series MAIN DIMENSIONS Model A B C D E F In. mm In. mm In. mm In. mm In. mm In
13 De Dietrich Gas 310/610 ECO Gas 610 ECO Series Base & leveling legs dimensions Mode
14 De Dietrich Gas 310/610 ECO 310-5 310-6 310-7 310-8 310-9Firing Sequence OperationMinimum Fuel Input MBH [kW] 205 [60] 256 [75] 311 [91
15 De Dietrich Gas 310/610 ECO Table 02, Technical data Flue gas temperature at 104/860F 126/52
16 De Dietrich Gas 310/610 ECO 4.3 GAS 310 ECO QUOTATION SPECIFICATION: Fully assembled cast aluminum floor standing sectional hot water
17 De Dietrich Gas 310/610 ECO 4.5 GAS 610 QUOTATION SPECIFICATION: Fully assembled cast aluminum floor standing sectional hot water b
18 De Dietrich Gas 310/610 ECO 5 EFFICIENCY INFORMATION 5.1 Combustion efficiency ▪ Theoretically efficiency up to 99.9% can be achieved
1 De Dietrich Gas 310/610 ECO Warning: Before you operate this boiler, read this manual carefully and take extra precautions to all safety and
19 De Dietrich Gas 310/610 ECO It is advisable (preferable) to install the Gas 310 ECO as follows: Place the crate c/w the boiler in th
20 De Dietrich Gas 310/610 ECO It is advisable (preferable) to install the Gas 610 ECO as follows: Place the crate c/w the boiler in the b
21 De Dietrich Gas 310/610 ECO 7.3 Flue gas discharge and air supply Venting 7.3.1 General The Gas 310/610 ECO is suitable for both convent
22 De Dietrich Gas 310/610 ECO 7.3.6 Conventional Chimney & CLV Systems Application Requirements: Warning: The boiler should never be
23 De Dietrich Gas 310/610 ECO 7.3.6 Continued CLV system application (Different Pressure Zones) This venting system uses two separate vent
24 De Dietrich Gas 310/610 ECO Table 05 - venting length chart. Table also applies to Gas 610 models. Warning & precautions: Venting
25 De Dietrich Gas 310/610 ECO 7.3.9 Vent terminations installation precautions: [Consult national & local codes for other requirements]
26 De Dietrich Gas 310/610 ECO 7.4 INSTALLATION DETAILS 7.4.1 Water pressure The boiler is suitable for a maximum working pressure of 100
27 De Dietrich Gas 310/610 ECO 1 ½ Cross TEE1 ½ In x ?? reducing bushing (if required) for relief valve as requiredRelief valve must be pipe
28 De Dietrich Gas 310/610 ECO 8 INSTALLATION INSTRUCTIONS FOR ELECTRICAL INSTALLER 8.1 General The De Dietrich Gas 310/610 ECO is suppl
2 De Dietrich Gas 310/610 ECO TABLE OF CONTENTS PREFACE 5 1. SAFETY INSTRUCTIONS 6 1.1 Symbols 6
29 De Dietrich Gas 310/610 ECO 8.2.4 Fuse ratings Fuses on the circuit board on the control unit: F1 – 2 AF mains voltage fuse (automati
30 De Dietrich Gas 310/610 ECO 8.3 Connections The terminal strips and boiler connectors can be seen once the control box cover is removed.
31 De Dietrich Gas 310/610 ECO 8.4 Wiring Diagram fig. 18 wiring diagram Fb 12AT
32 De Dietrich Gas 310/610 ECO 8.4 Wiring Diagram - Continued
33 De Dietrich Gas 310/610 ECO Field wiring examples (Additional wiring examples are supplied separately) Example 1, local modulation Typ
34 De Dietrich Gas 310/610 ECO 8.5 Switch sequence diagram 8.6 Boiler control 8.6.1 Gas 310 Introduction, Gas 610 each module Fig. 19
35 De Dietrich Gas 310/610 ECO 8.6.2 Gas 310 Modulating controls general (2 wire control) To make full use of the boiler’s modulating feat
36 De Dietrich Gas 310/610 ECO Gas 310 Temperature based 68 – 194°F [20-90°C] Set the value of the boiler control operation parameter
37 De Dietrich Gas 310/610 ECO Gas 610 Temperature based 68 – 194oF [20-90oC] set the value of the boiler control operation parameter to
38 De Dietrich Gas 310/610 ECO 8.7.4 Other outputs 8.7.5 Analog output Depending on the option settings in the service level (see section
3 De Dietrich Gas 310/610 ECO 8.3 Connections 30 8.4 Wiring diagram 31 8.5 Sequence of operation
39 De Dietrich Gas 310/610 ECO 8.8 Optional Inputs 8.8.1 System pressure sensor (optional) The system pressure sensor shutdown the boiler
40 De Dietrich Gas 310/610 ECO 8.8.5 Return butterfly valve 3-way valve (supplied by others) A butterfly valve should be installed in retur
41 De Dietrich Gas 310/610 ECO 9.0 INSTALLATION INSTRUCTIONS FOR GAS INSTALLER 9.1 Gas connection The Gas 310/610 is suitable for use with
42 De Dietrich Gas 310/610 ECO 10.0 COMMISSIONING Warning: If you do not follow the commissioning instructions exactly, a fire or explosi
43 De Dietrich Gas 310/610 ECO * For reference only. Measured combustion values more important. 17 Continued: a. Check and correct, if nece
44 De Dietrich Gas 310/610 ECO 18. Check gas leakage control and minimum gas pressure switch (if installed); Parameter must be set to a v
45 De Dietrich Gas 310/610 ECO 10.2 Shutdown 1. Switch off the on/off switch of the boiler. With this, a possible boiler control will be w
46 De Dietrich Gas 310/610 ECO 11.0 CONTROL AND SAFETY EQUIPMENT 11.1 General The boiler is supplied with a standard set of defaults pre
47 De Dietrich Gas 310/610 ECO 11.1.2 LED indicators The instrument panel has 4 indicating LED’s with the following functions: ▪ The LED ab
48 De Dietrich Gas 310/610 ECO 11.3 Display of value The display has only two digits available therefore values over this are displayed as
4 De Dietrich Gas 310/610 ECO Table 16 – Service level setting mode 54 13.2.1 Minimum fan speed 55 13.2.2
49 De Dietrich Gas 310/610 ECO 12.2 Read-out mode () Read-out mode is used to display various values. Press the key until appears i
50 De Dietrich Gas 310/610 ECO 12.3 Control strategy During normal operation, the boiler control can operate according to a specific strat
51 De Dietrich Gas 310/610 ECO 12.5 Counter mode ( , and ) (service level) 12.5.1 General The boiler control records various data on t
52 De Dietrich Gas 310/610 ECO 13.0 SETTING MODE 13.1 User level setting mode () Setting mode is used to change various settings to su
53 De Dietrich Gas 310/610 ECO 13.1.2 Pump run on time () Pump run on time can be adjusted (Please refer to installation contractor) -Pres
54 De Dietrich Gas 310/610 ECO Code Description Setting Range Factory setting Minimum fan speed (hundreds) see section 13.2.1 -
55 De Dietrich Gas 310/610 ECO 13.2.1 Minimum fan speed ( and ) Parameter , adjustable between 06 and 60 (x100 rpm) parameter , adjustab
56 De Dietrich Gas 310/610 ECO 13.2.8 T from control stops point to start point Parameter , adjustable from 9 to 36°F [5 to 20°C] This v
57 De Dietrich Gas 310/610 ECO Example (Factory setting is always = 0) ▪ Water pressure sensor on = 1 ▪ Analog output % = 0 ▪ Gas leakag
58 De Dietrich Gas 310/610 ECO 14 FAULT-FINDING 14.1 General • If the boiler does not start up, check the following: • Is a 120 V supp
5 De Dietrich Gas 310/610 ECO PREFACE Read t hese i nstructions c arefully, bef ore pu tting t he boi ler i nto op eration, f amiliarize
59 De Dietrich Gas 310/610 ECO 14.4 Failure (lock-out) codes (requires user intervention, manual reset of control) When a failure code is di
60 De Dietrich Gas 310/610 ECO Fan not operating - Fan defective - Fan cable is corroded, resulting in absence of voltage or control si
61 De Dietrich Gas 310/610 ECO 15 INSPECTION AND MAINTENANCE INSTRUCTIONS 15.1 General The De Dietrich Gas 310/610 ECO has been designed to
62 De Dietrich Gas 310/610 ECO 15.4 Maintenance If during the annual inspection combustion results indicate that the boiler is no longer ope
63 De Dietrich Gas 310/610 ECO 15.4.4 Cleaning the fan Use compressed air or a synthetic brush to clean the fan, be careful not to disturb
64 De Dietrich Gas 310/610 ECO 15.4.7 Cleaning the condensate collector Clean the condensate collector by removing the inspection cover (n
65 De Dietrich Gas 310/610 ECO 15.4.10 Gas filter check Measure the pressure differential P at measuring points, Pi and Pu (see fig. 37)
66 De Dietrich Gas 310/610 ECO 15.5 Exploded view and spare parts list (right hand version shown)
67 De Dietrich Gas 310/610 ECO Fig. 39 Exploded view Part # Description Item # Part # Description Item # boiler casing/frame Premix bur
68 De Dietrich Gas 310/610 ECO S54520 Access plate heat exchanger 5 sections 2028 S100488 Adapter 2" NPT (Gas inlet pipe) 3045 S54521
6 De Dietrich Gas 310/610 ECO 1 SAFETY INSTRUCTIONS 1.1 Symbols The f ollowing symbols are us ed in this d ocument to emphasize certain i
69 De Dietrich Gas 310/610 ECO 16 ADDENDICES
70 De Dietrich Gas 310/610 ECO 16.1 Control menu Fig. 40 Control menu flow chart
71 De Dietrich Gas 310/610 ECO 16.2 Shut-off codes
72 De Dietrich Gas 310/610 ECO 16.2 Shut-off codes (Continued) Table 25 Shut-off codes
73 De Dietrich Gas 310/610 ECO 17 BOILER COMMISIONING REPORT & MAINTENANCESCHEDULE 17.1 – Boiler Commissioning Report AddressLOCATION O
74 De Dietrich Gas 310/610 ECO 17.2 Boiler Control Settings Site Applied Boiler Control Settings: [Setting Mode] Advanced S
G310E 01 v1.0 04/2010DDR Americas Inc.1054 North DuPage AvenueLombard, Illinois 60148 USATel: 630-953-2374 / Fax: 630-953-23761090 Fountain Street Nor
7 De Dietrich Gas 310/610 ECO The boiler must not be modified or fitted with non OEM spare parts without the express written approval of DDR
8 De Dietrich Gas 310/610 ECO 3 DESIGN 3.1 Boiler Version Fig. 02 Cross-section Gas 310 ECO (Left hand boiler illustrated). G